JOINT “GB-P”
Application
Expansion Joints · Expansion Joints Wall/Wall

| Joint width | Joint orientation | Minimum “GB-MT” thickness | Seal (infill) | Supporting construction | Classification | Certificate |
| ≤ 120 mm | Horizontal on vertical construction | 1 mm along the lower and upper length of both faces | “GB-P” joint thickness 100 mm | Masonry or concrete walls with th. ≥ 150 mm, density ≥ 650 kg/m³ | EI 180 T-X-F-W120 | ETA 21/0116 |
Supply and installation of protection for horizontal expansion joints between walls, with max. width of 120 mm, EI 180 T-X-F-W120 fire resistance, with movement capability of up to 7,5%, made of “GB-P” JOINT SEALS, semi-rigid mineral fibre (density 150 kg/m3) treated on both sides with a layer of fire-protection putty, for a joint seal thickness of 100 mm, in accordance with classification report ETA 21/0116. It is necessary to measure the dimension of the joint to be sealed, transfer it onto the
strip and cut it using hand saws or utility knives, taking care to leave the cut-out slightly oversized with respect to the dimensions of the joint to be sealed. After fitting the “GB-P” JOINT SEAL, seal it laterally, on both faces, with the FIRESTOP SEALANT “GB-MT” to a minimum thickness of 1 mm.