JOINT “GB-P”
Application
Expansion Joints · Expansion Joints Floor/Wall

| Joint width | Joint orientation | Minimum “GB-MT” thickness | Seal (infill) | Supporting construction | Classification | Certificate |
| ≤ 120 mm | Horizontal | 1 mm along the lower and upper length of both faces | “GB-P” joint thickness 100 mm | Concrete floor slabs · Masonry or concrete walls with th. ≥ 150 mm, density ≥ 650 kg/m³ | EI 180 H-X-F-W120 | ETA 21/0116 |
Supply and installation of protection for horizontal expansion joints between floor slab and wall, with a max. width of 120 mm, fire resistance EI 180 H-X-F-W120, with movement capability of up to 7,5%, consisting of “GB-P” JOINTS, semi-rigid, in mineral fibre (density 150 kg/m3), treated on both sides with a layer of firestop compound, for a joint thk. of 100 mm, in accordance with classification report ETA 21/0116. It is necessary to measure the size of the joint to be sealed, transfer it onto the
strip and cut the strip using site handsaws or a cutter, taking care to leave the shape slightly oversized with respect to the dimensions of the joint to be sealed. After installing the “GB-P” JOINT, seal it laterally, on both faces, with FIRESTOP SEALANT “GB-MT” with a minimum thickness of 1 mm.