“GB-NE”
Application
Expansion Joints · Firestop Rope Joints Wall/Floor - With Induced Movement

| Joint width | Joint orientation | Supporting construction | Classification | Certificate |
| 10 mm ≤ x ≤ 60 mm | Horizontal | Reinforced concrete or concrete block floor slabs with th. ≥ 150 mm, density ≥ 600 kg/m³ · Masonry or concrete walls with th. ≥ 150 mm, density ≥ 600 kg/m³ | EI 120 H-M25-F-W10 to 60 | ETA 12/0119 |
Supply and installation of FIRESTOP ROPE “GB-NE” for the protection of horizontal joints between wall and floor slab with movement capability up to 25%, with fire resistance EI 120 H-M25-F-W10 to 60, consisting of a circular-section gasket made of two-component intumescent foam, diameter from 16 to 80 mm, in accordance with classification report ETA 12/0119.
The circular-section gasket must be inserted into the joint with slight compression, where it will remain in place, partly returning to its original dimensions through recovery expansion. A circular-section gasket must be inserted on each side of the joint. If necessary, the circular-section gasket can be cut with a utility knife.