UNIVERSAL FIRE COLLAR “GLOBAL COLLAR”
Application
Wall Penetrations · Penetrations Of Combustible Pipes

Supply and installation of UNIVERSAL FIRE COLLARS “GLOBAL COLLAR” with fire resistance EI 90/120 U/C U/U certified on masonry or plasterboard walls, consisting of a 45 mm wide metal band containing an intumescent wrap in accordance with classification report ETA 13/0640 and MPA NRW 210006105-2. Measure the diameter of the pipe to be protected and wrap the intumescent wrap around the pipe in the specified number of layers (see table). Count the specified number of metal band segments and break the band accordingly. Insert the dedicated brackets onto the metal band in a number
depending on the pipe diameter, and wrap the metal band around the pipe, clamping the two ends with the dedicated tabs. Fix the collar to the wall on both sides with metal expansion anchors Ø 6 or 8 mm. With plasterboard walls, use through threaded rods to fix the two collars. Before installing the collar, the remaining voids/gaps between the wall and the pipe shall be filled with dimensionally stable non-combustible material (concrete, cement mortar or gypsum) through the full thickness of the building element.