FIRE COLLARS “GB-C”
Application
Floor Penetrations · Penetrations Of Combustible Pipes

Supply and installation of FIRE COLLARS FOR COMBUSTIBLE PIPES “GB-C” with fire resistance EI 120 U/C certified on floor slabs, consisting of a metal shell 25/40/50/60 mm wide containing intumescent material in accordance with classification report ETA 11/0208. The collar must be wrapped around the pipe and fixed to the underside of the floor slab with metal expansion anchors, diameter 6 or 8 mm, in a number
depending on the diameter of the pipe to be protected. Before installing the collar, the remaining voids/gaps between the floor slab and the penetrating pipe must be filled with dimensionally stable non-combustible material such as concrete, cement or gypsum mortar, through the full thickness of the building element.