“FIREGUARD 18”
Application
Shaft Walls, Suspended Ceilings And Bulkheads · Box Enclosure For Air Diffuser

Supply and installation of PROTECTION FOR AIR DIFFUSERS with fire resistance REI/EI 60 certified on a membrane ceiling. To protect the air diffuser, it will be necessary to build an enclosure formed by two FIREGUARD® 18 boards, th. 2x18 mm, made of calcium silicates and sulphates, asbestos-free, in reaction to fire class A1. The boxing will be fixed at the base to a self-supporting structure consisting of “C” box profiles 100x50x0.6 mm, the upper side will be fixed to “L” profiles 30x30x0.6 mm At the penetration of the flexible air duct, made of aluminium and polyester with a steel wire spiral, an additional Fireguard 18 board will be screwed on. The duct will be protected by wrapping the INTUMESCENT WRAP “GB-T” for no. 16 turns and sealed externally with FIRESTOP SEALANT “GB-MT”, in conformity with classification report I.G. 394065/4224FR.