“FIREGUARD 18”
Application
Shaft Walls, Suspended Ceilings And Bulkheads · Box Enclosure For Air Conditioner

Supply and installation of PROTECTION FOR RECESSED AIR CONDITIONERS with fire resistance REI/EI 60 certified on a membrane ceiling. To protect the air conditioner, it will be necessary to build an enclosure formed by two FIREGUARD® 18 boards, th. 2x18 mm, made of calcium silicates and sulphates, asbestos-free, in reaction to fire class A1. The boxing will be fixed at the base to a self-supporting structure consisting of “C” box profiles 100x50x0.6 mm, the upper side will be fixed to “L” profiles 30x30x0.6 mm. At the pipe penetrations an additional FIREGUARD® 18 board will be screwed on. The pipes passing through the enclosure may be of the combustible, insulated multilayer or insulated metal type, or corrugated conduits containing electrical cables, and will be protected with the FIRE COLLAR “GLOBAL COLLAR PLUS” by wrapping the intumescent strip around the individual pipes for no. 2 layers, then cutting the metal sheet to a length sufficient for the overlap and wrapping it around the intumescent gasket, fixing it to the enclosure with no. 3 self-drilling metal screws, in conformity with classification report I.G. 394065/4224FR.