SEALANT “GB-MT”
Application
Expansion Joints · Vertical Wall/Wall

| Joint width | Joint orientation | “GB-MT” thickness | Seal (infill) | Supporting construction | Classification | Certificate |
| ≤ 30 mm | Vertical on vertical construction | 15 mm on both sides | rock mineral wool thickness 20 mm, density 40 kg/m³ | Masonry or concrete walls with th. ≥ 150 mm, density ≥ 650 kg/m³ | EI 240 V-X-F-W30 | ETA 21/0319 |
Supply and installation of protection for vertical expansion joints between walls: - with a maximum width of 50 mm, fire resistance EI 120 V-X-F-W50, with movement capability of up to 7,5%, consisting of a layer of rock mineral wool, thickness 60 mm, density greater than 33 kg/m3, and a layer of FIRESTOP SEALANT “GB-MT”, minimum thickness 10 mm. - with a maximum width of 30 mm, fire resistance EI 240 V-X-F-W30, with movement capability of up to 7,5%, consisting of a layer of rock mineral wool, thickness 20 mm, density 40 kg/m3, and a layer of FIRESTOP SEALANT “GB-MT” on both sides, minimum thickness 15 mm. In accordance with classification report ETA 21/0319.
The rock mineral wool panels must be inserted into the joint by light compression, where they will remain fixed, partly returning to their original size due to spring-back expansion, and the joint must then be sealed externally by applying a layer of FIRESTOP SEALANT “GB-MT” of suitable thickness.