“GB-P” PANELS and WRAP “GB-T”
Application
Wall Penetrations · Penetrations Of Insulated Pipes

Supply and installation of protection for penetrations of insulated metal or composite pipes with certified EI 60/120 fire resistance in masonry and plasterboard walls thickness ≥100 mm, consisting of INTUMESCENT WRAP “GB-T”, made of intumescent material 50 mm wide, and “GB-P” PANELS, semi-rigid mineral fibre (density 150 kg/m³), thk. 60 mm, treated on both sides with a layer of fire-protection coating, in accordance with ETA 21/0113. It is necessary to measure the dimensions and shape of both the opening to be sealed and the penetrating pipe, transfer them onto the “GB-P” PANELS and cut them using hand saws or utility knives, taking care to leave the cut-out slightly oversized with respect to the dimensions of the opening to be sealed. Apply a small amount of FIRESTOP SEALANT “GB-MT” to the sides of the cut-out or directly onto the inner
edge of the wall where the cut-out will be fitted. Fit the cut-out and insert it into the opening with an “interference” fit, then skim the joints with a spatula using the SEALANT “GB-MT”. It is necessary to position two “GB-P” PANELS butted together. In the case of a pipe insulated with expanded elastomers, the INTUMESCENT WRAP “GB-T” must be wrapped around the pipe to be protected, secured with adhesive tape to join its ends, and inserted into the gap remaining between the pipe and the “GB-P” PANELS. Insert the wrap on both sides of the wall. It is necessary to apply the number of layers indicated according to the pipe diameter (see table). The outer part may be sealed with SEALANT “GB-MT”.