FOAM “GLOBAL FOAM”
Application
Multiple Penetrations In Floors · Multiple Penetrations

Supply and installation of TWO-COMPONENT FIRESTOP FOAM “GLOBAL FOAM” with fire resistance EI 30/120 certified on floor slabs, for the sealing of multiple penetrations, consisting of high-expansion two-component firestop foam, in conformity with classification report ETA 11/0206. It is necessary to fill the opening starting from the bottom, dispensing the foam continuously to prevent it hardening inside the mixing nozzle. After approximately 2 minutes of curing, any foam residues protruding from the opening can be removed by cutting them with a knife. Any cables or pipes installed at a later stage can be routed through the existing foam. Holes left by removed cables or pipes
must be filled using the FOAM “GLOBAL FOAM”. If the opening has large free spaces, these can be filled using the BRICKS “GLOBAL BLOCK”. In the case of rectangular openings in floor slabs with a thickness between 150 and 250 mm, the required seal thickness can be achieved by lining the inside of the opening with two layers of FIREGUARD® 13 boards, thickness 2x12.7 mm, or by boxing out the opening externally with calcium silicate boards. In the case of circular openings in floor slabs with a thickness between 150 and 250 mm, the required seal thickness can be achieved by boxing out the opening externally with calcium silicate boards.