FIRE COLLAR “GLOBAL COLLAR PLUS”
Application
Penetrations In Shaft Walls, Suspended Ceilings And Bulkheads · Multiple Penetrations

Supply and installation of UNIVERSAL FIRE COLLAR “GLOBAL COLLAR PLUS” for the protection of combustible corrugated conduits containing electrical cables, single electrical cables, steel chains and threaded rods, with fire resistance REI 120 certified on a 200 mm thick hollow clay block floor slab protected by an accessible suspended ceiling; the collar consists of a metal shell of thin steel sheet, nominal section 40x30x0,5 mm, containing a graphite-based intumescent gasket, nominal section 40x2 mm, in accordance with ETA 23/0843. The collar must be installed
simply resting on the top face of the suspended ceiling panelling; to apply the collar, measure the diameter of the bundle of services to be protected and wrap the intumescent wrap 2 times around the bundle; break off a length of metal sheet sufficient for the overlap and wrap it around the intumescent gasket, closing it with a metal screw.